TSA1
Addressable fire detection and suppression control panel 1 Loop.
- Addressable fire detection and extinguishing control panel.
- The characteristics indicated refer to the TSA1 EXTENDED configuration.
- Equipped with a detection loop and an Extinguishing Unit (EDU).
- The detection loop can handle up to:
- 199 detectors.
- 99 modules.
- 9 TSM1 modules (EDU peripheral extinguishing channels).
- 2 RS485 serial buses for connection of expansion devices, up to 5 devices selectable between:
- Repeater panels.
- Communication devices.
- The serial buses also allow networking of Tecnofire control units.
- Management of:
- 150 detection zones.
- 100 alarm plans.
- 8 slots.
- Advanced management using formula-based logic that dynamically relates the operating states of system devices:
- 100 formulas.
- 100 virtual detection zones.
- The centre is equipped with:
- 3 specialised signalling outputs.
- 2 freely programmable signalling outputs.
- The integrated EDU has:
- 3 conventional detection zone inputs.
- 7 controlled inputs for the management of actuation and control devices.
- 2 controlled outputs for managing extinguishing valves.
- 2 controlled outputs for the management of optical-acoustic alarm devices.
- 5 specialised signalling outputs.
- Automatic or manual operation mode.
- Extinguishing cycle with 5 modes of execution.
- Centralised or local management of up to 10 independent EDUs, with local or centralised extinguishing cycle control, also in switched mode.
- User interface consisting of:
- 4.3" colour display.
- Soft touch keyboard for programming and management.
- 33 LEDs for signalling.
- Multi-function acoustic buzzer.
- RSC® system management: programming, remote management and control.
- Customisable or permanent four-year calendar management.
- Event memory managed with FIFO logic with capacity for 8192 events.
- 2.7 A modular switched-mode power supply.
- Battery capacity: 2 × 12 V - 7 Ah.
- ABS and steel housing.
- Surface mounting or by means of optional adapters in a 19" rack cabinet.
- Degree of protection: IP3x.
- Available colours: white, grey, red, yellow.
- Dimensions (L × W × D): 440 × 345 × 146 mm.
- Approvals:
- EN 54-2:1997 + A1:2006.
- EN 54-4:1997 + A1:2002 + A2:2006.
- EN 12094-1:2003.
- Certification: 0051-CPR-2816.
- System compatibility: UNI EN 54-13:2020.